Key Technical Criteria for Selecting a Shell & Tube Heat Exchanger

Shell & tube heat exchangers are preferred in many industries, from chemicals to energy and from food processing to marine applications, thanks to their resistance to high pressure and temperature, robust construction and flexible design options. However, whether these advantages are realized in the field depends on the unit being designed to suit the process.

An incorrectly selected shell & tube heat exchanger results in insufficient capacity, rapid fouling, premature corrosion, tube leaks and difficult maintenance. So which technical criteria should be considered for the right selection? Let’s go through them step by step.


1. Process Data: Capacity, Flow Rates and Temperatures

The first step in the right selection is to fully define the process data for the hot and cold sides. The thermal calculation is based on this data; missing or estimated data means an oversized or undersized unit.

• Heat duty (kW): The amount of heat to be transferred.
• Flow rates (m³/h or kg/s): The flow on both sides.
• Inlet and outlet temperatures (°C): At least three of the four temperatures must be known.
• Phase change: Is one of the fluids condensing or evaporating (condenser, evaporator, steam heating)?
• Operating regime: Does the unit run continuously, under variable load or seasonally?

In shell & tube heat exchangers, the flow arrangement directly affects the temperature program. In multi-pass designs (for example, 1 shell pass – 2 tube passes), the flow is not true counterflow. Therefore, if the cold side outlet temperature exceeds the hot side outlet temperature (temperature cross), a single shell may not be sufficient; multiple shells in series or a counterflow design is required.

In practice, an approach temperature below 3–5 °C is not economical for shell & tube heat exchangers; if closer temperatures are required, a plate heat exchanger should also be considered. For more details, see our article When Should Shell & Tube Heat Exchangers Be Preferred?

2. Fluid Allocation: Which Fluid Goes in the Tubes, Which in the Shell?

One of the most critical decisions specific to shell & tube design is which side each fluid is allocated to. This decision directly determines the cost, ease of cleaning and service life of the unit.

As a general rule, dirty, scale-forming or particle-laden fluids are placed on the tube side. Corrosive fluids such as seawater and chemicals, high-pressure and high-temperature fluids, and cooling tower water are also generally preferred on the tube side.

The shell side, on the other hand, is better suited to viscous fluids such as oil, low-flow fluids, condensing steam, fluids requiring low pressure drop, and clean fluids.

The logic is simple: the inside of the tubes is much easier to clean mechanically than the shell. When a corrosive or high-pressure fluid is placed in the tubes, expensive materials and thick walls are only needed for the tubes and channels; the shell can be made of an economical material.

3. Flow Velocity and Allowable Pressure Drop

Flow velocity balances heat transfer, fouling and erosion. Low velocity accelerates fouling, while high velocity leads to erosion, vibration and high pumping energy.

• Tube side (water): A range of 1–2.5 m/s is generally targeted. For copper alloy tubes, the upper limit is kept lower due to the risk of erosion.
• Shell side (liquid): Generally designed in the range of 0.3–1 m/s.
• Pressure drop: For liquids, typically 0.3–0.7 bar per side; however, the deciding factor is what the existing pump can handle.

Pressure drop is the most frequently overlooked parameter in selection. If the allowable pressure drop is specified at the outset, the number of tube passes, baffle spacing and number of tubes are optimized accordingly. The density and viscosity of the fluid, and how these change with temperature, must also be taken into account in the calculation; especially with viscous fluids such as oil, this is the main factor determining performance.

4. Material Selection and Corrosion Resistance

Material selection is the most important factor determining the service life of a shell & tube heat exchanger. The advantage of this design is that the tubes, tube sheet, shell and channels can each be made of a different material depending on the fluid they are in contact with.

Typical tube material options by application can be summarized as follows:

Carbon steel: Used for clean water, oil, steam and closed-loop systems; generally preferred as the shell material.

Stainless steel (AISI 304 / 316L): Common in food, pharmaceutical, chemical and process water applications.

Copper and copper-nickel (CuNi 90/10): Suitable for cooling, refrigerant applications and seawater.

Titanium: Stands out for seawater, high-chloride and aggressive environments.

Duplex stainless steel: Preferred in processes with a risk of chloride-induced stress corrosion cracking.

The final choice depends on the fluid chemistry, temperature, chloride content and flow velocity.

Particular attention should be paid where different metals are used together. If the tube and tube sheet materials are incompatible, galvanic corrosion may occur. In addition, the difference between the thermal expansion coefficients of the shell and tube materials also affects the choice of construction type.

For more details, see our article Corrosion in Heat Exchangers: Causes, Signs, and Prevention Methods.

5. Construction Type and Tube Layout

In shell & tube heat exchangers, the construction type determines how thermal expansion is accommodated and which side can be cleaned. Fixed tube sheet, U-tube and floating head types differ in terms of thermal expansion, cleaning and cost:

Fixed tube sheet: The most economical option. However, its ability to accommodate thermal expansion is limited; an expansion joint is required in applications with a high temperature difference. The tube side is easy to clean, while the shell side can only be cleaned chemically.

U-tube: A medium-cost solution. Since the tubes can expand freely, thermal expansion is not a problem. The shell side is easy to clean; however, cleaning the inside of the tubes is difficult because of the bends.

Floating head: The most expensive type. It allows free thermal expansion, and both the tube and shell sides can be cleaned mechanically.

The tube layout also affects selection. A triangular (30°) layout fits more tubes into the same shell and increases heat transfer, but does not allow mechanical cleaning between the tubes. A square (90°) layout provides cleaning access for fouling fluids on the shell side. 5/8″ and 3/4″ are common tube diameters; for fouling fluids, larger-diameter tubes reduce the risk of clogging.

For more details, see our article What Are the Types of Shell and Tube Heat Exchangers? Which One Is Used in Which Application?

6. Design Conditions, Fouling Factor and Ease of Maintenance

A heat exchanger should be designed not only for normal operating conditions but for the most demanding conditions that may occur in the system.

• Design pressure and temperature: Should be defined separately for each side, taking into account pump shut-off pressure, water hammer and safety valve setting.

• Standards: The unit should be designed and tested in accordance with relevant standards and regulations such as TEMA, ASME or PED (2014/68/EU).

• Fouling factor: Additional surface is added to the design to allow for fouling that builds up over time. It should be selected realistically based on the fluid type.

• Maintenance space: To allow the tube bundle to be pulled, clear space at least equal to the bundle length should be left in front of the unit.

A common mistake regarding the fouling factor is the idea that “the more, the safer.” Excessive surface margin reduces flow velocities and accelerates fouling even further. Therefore, the fouling factor should be determined based on the actual character of the fluid and the planned maintenance interval.
For more details, see our article Cleaning and Maintenance Guide for Shell & Tube Heat Exchangers.

Checklist Before Requesting a Quote

Preparing the following information allows the thermal and mechanical calculations to be carried out quickly and accurately:

• Heat duty (kW) and flow rates on both sides
• Inlet and outlet temperatures; phase change information, if any
• Fluid types and physical properties (density, viscosity, additive concentration)
• Allowable pressure drop for each side
• Design pressure and design temperature
• Fouling/particle content and chloride content of the fluid
• Preferred materials and applicable standard (TEMA, ASME, PED)
• Installation orientation (horizontal/vertical) and space available for maintenance

Conclusion

Selecting a shell & tube heat exchanger is not just about a capacity value; it is an engineering process in which process data, fluid allocation, flow velocity, materials, construction type and maintenance needs are evaluated together. A correctly selected shell & tube heat exchanger pays off with low operating costs and many years of trouble-free operation.

At Refkar Soğutma, we perform thermal and mechanical calculations based on your process data and determine the material, tube layout and construction type specifically for your application. For technical support on your project, please contact us.